THW-2-LS / THHW-LS
Building wire

THW-2-LS / THHW-LS

Mexican-market building conductor reference with low-smoke PVC insulation.

Latin America
Sizes, construction & electrical data
THW-2-LS / THHW-LS / TECHNICAL DATA

Sizes, construction & electrical data

Copper / PVC · 600 V · 90°C

Insulation material
PVC, low smoke / low acid gas
Operating temperature
90°C dry/wet; 60°C in oil
Ampacity basis
NOM-001-SEDE Table 310-15(b)(16), conduit, ambient 30°C
Reference voltage
600 V reference
Copper / PVC · 600 V · 90°C
ConfigurationNominal area / conductormm²Strands per conductorInsulation wallmmOverall dimensions / diametermmApproximate cable weightkg/kmReference ampacity, 60°C columnAReference ampacity, 75°C columnAReference ampacity, 90°C columnASelection
14 AWG2.08190.763.430152025
12 AWG3.31190.763.950202530
10 AWG5.26190.764.570303540
8 AWG8.37191.145.9110405055
6 AWG13.3191.527.6170556575
4 AWG21.2191.528.8250708595
2 AWG33.6191.5210.338095115130
1/0 AWG53.5192.0313.2600125150170
2/0 AWG67.4192.0314.3740145175195
3/0 AWG85192.0315.6910165200225
4/0 AWG107192.03171130195230260
250 kcmil127372.41191350215255290
300 kcmil152372.4120.31590240285320
350 kcmil177372.4121.61820260310350
400 kcmil203372.4122.72080280335380
500 kcmil253372.4124.82550320380430
600 kcmil304612.7927.63070350420475
750 kcmil380612.7930.23840400475535
1000 kcmil507612.79345040455545615

Typical applications

Low-voltage distribution in buildings and industrial facilities.

Design advantages

Low-smoke design with heat and moisture resistance.

Selection notes

LS does not mean halogen-free. Mexican requirements do not automatically apply across Latin America.

Standards to review

NMX / NOM