FOR IMPORTERS, DISTRIBUTORS & RETAIL PROGRAMSSales Department · (+84) 868 848 620
H07V-K
Building wire

H07V-K

Flexible PVC insulated single core for protected fixed installations.

Europe
Sizes, construction & electrical data
H07V-K / TECHNICAL DATA

Sizes, construction & electrical data

Class 5 copper / PVC TI1 · 450/750 V

Conductor / insulation
Class 5 bare copper / PVC TI1
Temperature, fixed / flexed
−30…+70°C / −5…+70°C
Minimum bend radius, fixed / flexed
6D / 12D
Reference voltage
U₀/U 450/750 V
Class 5 copper / PVC TI1 · 450/750 V
Configurationcores × mm²Nominal area / conductormm²Overall dimensions / diametermmMaximum individual strand diametermmMaximum DC resistance at 20°CΩ/kmApproximate cable weightkg/kmSelection
1 × 1.51.52.90.2613.320
1 × 2.52.53.60.267.9831
1 × 444.10.314.9546
1 × 664.70.313.375
1 × 10106.10.411.91125
1 × 16167.30.411.21199
1 × 252590.410.78299
1 × 353510.20.410.554421
1 × 505012.10.410.386539
1 × 707013.80.510.272730
1 × 959516.30.510.206973

Typical applications

Control cabinets, equipment and protected conduit wiring.

Design advantages

Fine-stranded conductor eases panel routing.

Selection notes

Flexible conductor does not imply continuous-flex service. Confirm CPR declaration where applicable.

Standards to review

EN 50525-2-31

Related cable families

TGS · VIETNAM

Let’s connect your next project.

Send your cable type, destination market and volume. We will review the next steps with you.